The general SNS pressure switches are widely used in fluorinated refrigerants, air and water control applications, with wide operating temperature range from -20°C to 120° C. Key features include;
a. Option for drip proof enclosure for marine application or explosion proof for special application
b. Stainless steel model available upon request
c. High durability
|
Range (MPa) |
Differential (MPa) |
Max. (MPa) |
Min. |
Max. |
Min. |
Max. |
SNS-C101X |
-0.06 |
0.1 |
0.015 |
0.05 |
0.3 |
SNS-C102X |
-0.02 |
0.2 |
0.025 |
0.15 |
0.5 |
SNS-C103X |
-0.06 |
0.3 |
0.035 |
0.2 |
1 |
SNS-C104X |
-0.06 |
0.4 |
0.04 |
0.2 |
1.5 |
SNS-C106X |
-0.06 |
0.6 |
0.06 |
0.4 |
1.5 |
SNS-C110X |
0.1 |
1 |
0.1 |
0.3 |
1.5 |
SNS-C120X |
0.5 |
2 |
0.2 |
0.5 |
3 |
SNS-C130X |
0.5 |
3 |
0.3 |
1 |
3.3 |
SNS-C135X |
1 |
3.5 |
0.5 |
1.5 |
3.8 |