DewPro MMY35 - Specifications
Supply Power 24 VDC nominal (9 to 32 VDC)
Current Loop 4 mA to 20 mA corresponding to a standard dew point
range of -90°C to +10°C (-130°F to +50°F)
Communication RS 485, DewPro protocol
Cable Connector

Rating IP 65; Pins 1 (+) (red) and 2 (-) (black) = current loop supply power; 3 (-) (brown) and 4 (+) (yellow) = RS 485 communication. Pins 5 through 8 (green, white, orange, blue) are not being used for the loop-powered version.

Sensing Element Planar gold, aluminum oxide, capacitance principle
Calibration Range -90°C to +10°C (-130°F to +50°F) dew point temperature
Recommended Recalibration Cycle 6 to 24 months, depending on application and required accuracy
Calibration Accuracy +/- 2°C (+/- 3.6°F) dew point at 20°C (68°F) ambient temperature
Repeatability +/- 1°C (+/- 1.8°F)
Sintered Filter 100 micron
Maximum Relative Humidity 50% at dew point temperatures >0°C (32°F)
Temperature Coefficient < 0.2°C/°C (< .36°F/°F)
Ambient and Storage Temperature -40°C (-40°F) to +50°C (+122°F)
Nominal Operating Temperature -20°C (-4°F) to +40°C (+104°F)
Maximum Operating Pressure 150 psig (10 bar)
Helium Leak-rate < 10-6 mbar l/s
Maximum Gas Velocity 50 m/s at 1 bar, 5 m/s at 10 bar
Probe Mounting Adapter Stainless steel 316 (1.4571) with G 1/2 thread (DIN/ISO 228) and O-ring seal
Rating IP 40
Wrench Width 30 mm
Protection from Particles Protective cap with 10 micron filter
Weight 0.55 lbs. (250 grams)